An ASCE 7-22 ponding analysis gives you a water profile, not one rain load for the bay. This article covers how to put that water on steel joists and girders without overloading or underloading them.
Under ASCE 7-16, ponding was a separate stability check and never part of the member load.[1] Under ASCE 7-22 it is part of , and the usual shortcuts miss in both directions: on the example bay, a uniform load overstates joist moment by 47% and a trapezoid understates it by 21%.
This is the companion to how to calculate ponding head for ASCE 7-22 and uses the same bay. Not every jurisdiction has adopted ASCE 7-22, so confirm the edition first.
Ponding Loads on Joists and Girders at a Glance
| Step | What to do | On the example bay |
|---|---|---|
| Joist load shape | Point loads from the analysis, or any shape that stays on top of the water | Uniform at the low-point value: +47% moment. Trapezoid at the roof slope: −21% |
| Load across the joists | Middle joist's load on every joist, or each joist's own | 23.4 psf at the columns, 41.2 psf at the middle joist |
| Girders | Joist end reactions as point loads | Largest at midspan, where the girder sags most |
| Load combinations | takes the or slot | LRFD psf at the low point |
| Joist schedule | Minimum shear of 12.5% of the maximum end reaction | Covers shear reversal from water at the low end |
| Reducing the load | Keep the overflow inlet low, stiffen the girder | A W21×44 girder takes from 41 to 28 psf |
The Example Bay
A 30 × 30 ft interior bay of a single-story retail building in Bentonville, Arkansas, from the companion article on calculating ponding head:
- Framing: W16×26 girders, 16K3 joists at 5 ft on center, sized for at L/240
- Slope: 1/4 in. per ft along the joists, low edge along a girder
- Dead load: psf
- Water level: 4.5 in. above the low point, so psf
- Iterative ponding analysis: 7.92 in. of water at the low point of the middle joist, so psf and in.
Every number below comes from that analysis, run in the free rain load and ponding calculator.
Load the Joists as the Water Sits
ASCE 7-22 Section 8.2 requires each portion of the roof to carry the water that accumulates on it.[2] On a sloped, deflected joist that water is deepest at the low end and runs out before the high end, so whatever load you apply has to stay on top of it along the whole span. Common shapes on the middle joist, against the analysis's own point loads (unfactored rain only):
| Load shape on the joist | Moment | Shear |
|---|---|---|
| Point loads from the analysis | exact | exact |
| Trapezoid: 41.2 psf at the low edge, falling at the roof slope | −21% | −15% |
| 41.2 psf uniform over the whole joist | +47% | +25% |
| 41.2 psf for 12 ft from the low edge, then tapering to zero at the high edge | +14% | +10% |
| 27.9 psf uniform (equal moment) | about 0% | −16% |
- Trapezoid: ignores the sag, so it drops below the water near the low end.
- Equal-moment uniform load: misses shear, because the water is heaviest at the low end.
- Uniform : the simplest safe shape, at 47% extra moment. Flat for 12 ft, then tapered, costs 14%.
Each Joist Carries Its Own Rain Load
The girder doesn't deflect at the columns, so the joists on the column lines carry only psf at the low end. The load peaks at the middle joist, 41.2 psf, where the girder sags most.
Using the middle joist's loading for every joist is simple and conservative. The girders take the joist end reactions as point loads, not psf over a tributary width.
Load Combinations: Takes the or Slot
In ASCE 7-22, including ponding goes into the basic combinations with no further ponding check. The ponding analysis itself uses unfactored loads (Design Guide 40 Sections 2.2 and 2.3).[2,3]
| ASCE 7-22 combination | Load | At the low point of the middle joist |
|---|---|---|
| LRFD 3a (Section 2.3.1) | psf | |
| ASD 3a (Section 2.4.1) | psf |
is also a companion load in LRFD 2a and 4a and ASD 4a and 6a. For ASD , Design Guide 40 Section 2.3 allows the load effects from the ponding analysis to be used directly.[3]
Specify a 12.5% Minimum Joist Shear
Joists are designed for uniform load. Water piled at the low end can move the peak moment off midspan and reverse shear near midspan, putting tension webs in compression. Design Guide 40 Section 2.5 recommends a minimum shear of 12.5% of the maximum end reaction, which the SJI Roof Bay Analysis Tool also assumes.[3] Put that note on the joist schedule.
What Reduces the Ponding Rain Load
At the low point, is the water the drains hold, , times what the sag does to it: psf. Drainage choices move ; framing choices move the multiplier. The figure changes one thing at a time.
| Change | Effect on at the low point |
|---|---|
| Overflow inlet height | Each inch adds 5.2 psf to and 8 to 12 psf to |
| Bay size, 30 × 30 ft to 40 × 40 ft | 41 to 59 psf, with members sized for the same loads |
| Stiffer girder, W16×26 to W21×44 | 41 to 28 psf |
| Stiffer joists (L/360) or more joists | Barely changes |
Set the overflow inlet early. It is the largest lever. Design Guide 40 Section 2.9 suggests assuming a 2-in. inlet and 4 in. of hydraulic head until the drains are designed, then confirming by RFI before construction drawings go out.[3] Moving the inlet during design is a line on the plumbing sheet; after the framing is set, it is heavier steel.
Iterate on long bays. From 30 × 30 ft to 40 × 40 ft, the Design Guide 40 amplification factor climbs from 2.4 to 7.2, far faster than the load itself, and Design Guide 40 notes loses accuracy as it grows.
Why more joists barely help. For a joist sized exactly to a deflection limit of L/n under a load , substituting into ASCE 7-22 Commentary Equation C8.2-6 gives:
This is my derivation, not a published equation. The spacing drops out, because closer joists are each sized lighter. The design load is in the denominator, which is why light roofs in low-snow climates are the most flexible.
The Bottom Line
Put the ponding water on the joists as point loads or a shape that stays on top of it, put the joist end reactions on the girders, and specify the 12.5% minimum joist shear. Before the framing is set, check the overflow inlet height and the girder, because they move the load far more than the joists do. For the rain load itself, Prose carries your ponding head into for every region and drainage zone on the project, with each step cited in the report.
Frequently Asked Questions
How should ponding rain load be applied to steel joists?
How is ponding rain load applied to girders?
Which ASCE 7-22 load combinations include the rain load?
Why do joists need a minimum shear for ponding?
What reduces ponding rain load the most?
Related Resources
- How to calculate ponding head for ASCE 7-22: the Design Guide 40 method and the iterative analysis worked on this bay, and why they give different answers
- Rain load calculation per ASCE 7: the SDSL rules, static and hydraulic head, the design storm by Risk Category, and what changed across editions
- Free rain load and ponding calculator: one bay, iterative ponding analysis, ASCE 7-22 and 7-16 rain loads side by side, with a calc report
If you read this provision differently or have run into it applied another way on a real project, reach out at support@prose-eng.com. I'm a practicing engineer, not an infallible one.
See a real loads package, fully cited
Wind, snow, seismic, rain — generated across ASCE 7-10/16/22 with every step traced to code.
Review a sample reportReferences
- American Society of Civil Engineers. Minimum Design Loads and Associated Criteria for Buildings and Other Structures(ASCE/SEI 7-16), Selected provisions and commentary. Reston, VA:ASCE, 2016.
- American Society of Civil Engineers. Minimum Design Loads and Associated Criteria for Buildings and Other Structures(ASCE/SEI 7-22), Selected provisions and commentary. Reston, VA:ASCE, 2022.
- American Institute of Steel Construction and Steel Joist Institute. AISC/SJI Design Guide 40: Rain Loads and Ponding. Chicago:AISC/SJI, 2024. Replaces AISC 360-16 Appendix 2, which was removed from AISC 360-2022.